				General specifications
			 | 
		
		
			| 
				Number of protected signal lines
			 | 
			
				1
			 | 
		
		
			| 
				Functional safety related parameters
			 | 
		
		
			| 
				Safety Integrity Level (SIL)
			 | 
			
				SIL 3
			 | 
		
		
			| 
				Supply
			 | 
		
		
			| 
				Rated voltage
			 | 
			
				≤ 48 V
			 | 
		
		
			| 
				Rated current
			 | 
			
				≤ 250 mA
			 | 
		
		
			| 
				Leakage current
			 | 
			
				≤ 5 μA
			 | 
		
		
			| 
				On-state voltage
			 | 
			
				≤ 85 V
			 | 
		
		
			| 
				Ground insulation
			 | 
			
				≥ 500 V breakdown voltage
			 | 
		
		
			| 
				Electrical specifications
			 | 
		
		
			| 
				Total discharge current (8/20 μs)
			 | 
			
				20 kA
			 | 
		
		
			| 
				Conformity
			 | 
		
		
			| 
				Degree of protection
			 | 
			
				IEC 60529:2001
			 | 
		
		
			| 
				Ambient conditions
			 | 
		
		
			| 
				Ambient temperature
			 | 
			
				-30 ... 60 °C (-22 ... 140 °F) For usage in hazardous area observe EC-type examination certificate.
			 | 
		
		
			| 
				Mechanical specifications
			 | 
		
		
			| 
				Housing material
			 | 
			
				Stainless steel 1.4401 (AISI 316) 
surface all over polished
			 | 
		
		
			| 
				Degree of protection
			 | 
			
				IP67
			 | 
		
		
			| 
				Cable
			 | 
			
			 | 
		
		
			| 
			 | 
			
				Length
			 | 
			
				0.3 m
			 | 
		
		
			| 
				Mass
			 | 
			
				approx. 200 g
			 | 
		
		
			| 
				Dimensions
			 | 
			
				AF22 x 77 mm (0.9 x 3 inch)
			 | 
		
		
			| 
				Mounting
			 | 
			
				M20 x 1.5 thread
			 | 
		
		
			| 
				Data for application in connection with hazardous areas
			 | 
		
		
			| 
				EU-type examination certificate
			 | 
			
				PTB 00 ATEX 2175
			 | 
		
		
			| 
			 | 
			
				Marking
			 | 
			
				  II 2G EEx ia IIC T6
			 | 
		
		
			| 
			 | 
			
				Voltage
			 | 
			
				50 V
			 | 
		
		
			| 
				Maximum leakage current
			 | 
			
				10 kA line to ground (common), 5 kA line to line (differential) in accordance to IEC 60-2
			 | 
		
		
			| 
				Nominal response time
			 | 
			
			 | 
		
		
			| 
			 | 
			
				Symmetrical
			 | 
			
				1 ns
			 | 
		
		
			| 
			 | 
			
				Asymmetric
			 | 
			
				100 ns
			 | 
		
		
			| 
				Bandwidth
			 | 
			
				≥ 40 kHz
			 | 
		
		
			| 
				Directive conformity
			 | 
			
			 | 
		
		
			| 
			 | 
			
				Directive 2014/34/EU
			 | 
			
				EN 60079-0:2012+A11:2013 , EN 60079-11:2012
			 |